Breaker & Wire Size Chart

The reference table every homeowner Googles mid-project — with straight answers on when to stop DIYing.

Breaker Size → Wire Size (Copper)

Breaker SizeCopper Wire (THHN/NM)Typical Uses
15 amp14 AWGLighting circuits, bedroom outlets
20 amp12 AWGKitchen & bath outlets, garage, microwave
30 amp10 AWGElectric dryer, water heater, RV outlet
40 amp8 AWGElectric range, larger AC units, EV charging (32A)
50 amp6 AWGRanges, spas, EV charging (40A), welders
60 amp6–4 AWGSub-panels, EV charging (48A), large AC
100 amp3–1 AWGSub-panels, casitas, workshops
200 amp2/0 copper / 4/0 aluminum SEMain service

The rule underneath the table: the breaker protects the wire, not the appliance. When in doubt, bigger wire is always safe; a bigger breaker never is.

Common Circuits Cheat Sheet

Appliance / CircuitTypical BreakerNotes
Central AC (3–5 ton)30–60 amp (2-pole)Match the unit’s nameplate — not a guess
Electric dryer30 amp (2-pole)10 AWG, 4-prong outlet on new work
Electric range/oven40–50 amp (2-pole)8–6 AWG
EV charger (Level 2)40–60 amp (2-pole)80% rule: 48A charging needs a 60A circuit
Microwave (built-in)20 amp dedicated12 AWG
Dishwasher / disposal15–20 ampOften dedicated; GFCI in current code
Pool pump20 amp (typically 2-pole)GFCI-protected, bonded
Bathroom outlets20 amp GFCIRequired dedicated in modern code

Modern code adds requirements these tables can’t capture — AFCI/GFCI protection, dedicated circuits, and derating for conduit fill and Arizona attic temperatures. That’s the part licensed electricians carry in their heads.

FAQ

Common Questions

Can I put a bigger breaker on the same wire to stop trips?

Never. Breaker size exists to protect the wire — a 30-amp breaker on 14-gauge wire lets the wire cook inside your wall before the breaker notices. If a circuit trips constantly, the fix is finding the overload or running a new circuit.

Copper vs. aluminum wire sizes — why the difference?

Aluminum conducts less per size, so it must be thicker for the same amperage (e.g., 4/0 aluminum vs 2/0 copper for a 200A service). Aluminum is standard and safe for large feeders; it’s the old small-gauge aluminum branch wiring that causes trouble.

Do these charts make DIY electrical legal in Arizona?

Homeowners can pull permits for some work on their own primary residence, but anything beyond a like-for-like swap deserves a licensed hand — and unlicensed paid work over $1,000 is illegal in Arizona. Use the charts to understand your system and check the work you hire.

Project Bigger Than a Chart?

Flat-rate circuits, permits included, done right.